How to wire the level transmitter

by:Sure     2021-08-08
There is a liquid level indicator on the spot that should have a DC24V feed output, otherwise the transmitter will not work normally. The correct connection method should be 1 transmitter + and-terminals 2 display meter input signal + and-terminals 3 DC24V feed output + and-terminals to connect the above three groups of 6 terminals in + and-order in series into one Loop. It should be noted that the input signal of the display meter should be set to 4-20mA. There is a liquid level display meter on site and it should have a DC24V feed output, otherwise the transmitter will not work normally. The correct connection method should be 1 transmitter + and-terminals 2 display meter input signal + and-terminals 3 DC24V feed output + and-terminals to connect the above three groups of 6 terminals in + and-order in series into one Loop. Note that the input signal of the display meter should be set to 4-20mA current. In addition, some meters short-circuit the DC24V feeder-terminal and the display meter input signal + terminal inside the meter. You can refer to the instruction manual of the relevant meter. Test is a test terminal, you can use a multimeter to measure the 4-20mA current in the loop without removing the wires on the + and-terminals