Contact Us Right Away
If you run into any issue or have any question.
Ultrasonic Magnetic Vortex Flow Meter Manufacturer, Sure We Are, Sure To Be Better | ✉ overseas@suremeter.com
Before installing a swirl flow meter, it's crucial to understand not only the installation methods but also the precautions to take. This knowledge helps minimize potential issues during the installation process.
Proper Installation Methods for Swirl Gas Flow Meters
If not installed and maintained correctly, swirl flow meters can experience reduced measurement accuracy and performance issues. Here's how to install them correctly:
Handling and Hoisting: When moving or hoisting the flow meter, use lifting slings around the neck of the meter's flanges. Avoid inserting pipes into the measuring tube for hoisting to prevent damaging the lining. Also, protect the wiring socket from impact damage.
Alignment and Grounding: Ensure the center of the swirl flow meter aligns with the center of the process pipeline. Proper grounding is essential to prevent measurement errors.
Precautions for Installing Swirl Flow Meters
Installation Angle: The flow meter can be installed at any angle, but the direction of flow must match the arrow on the meter indicating the direction of flow.
Avoid Interruptions and Pulsations: Swirl flow meters should not be used in applications where flow frequently interrupts or where there are strong pulsating flows or pressure fluctuations.
Expansion and Flexibility: Consider installing expansion joints or bellows in the pipeline to prevent severe stretching or breaking of the flow meter.
Environment: Install the flow meter in areas free from strong electromagnetic fields, intense mechanical vibrations, and thermal radiation.
External Power Supply: When using an external power source, ensure the flow meter is correctly and stably grounded. Do not share grounding wires with high-power systems. Avoid connecting the welding system's ground wire to the flow meter during installation or maintenance.
Outdoor Installations: If the flow meter is installed outdoors, it should have a cover to protect it from rainwater and direct sunlight, which can affect the lifespan of the meter.
By following the correct installation methods and heeding the necessary precautions, you can ensure the accurate and reliable operation of your swirl flow meter. Proper installation is key to achieving optimal performance and a long service life from your flow measurement equipment.
Copyright © 2025 Tianjin Sure Instrument Co., Ltd. | All Rights Reserved 津ICP备08002549号-2
Hello, please leave your name and email here before chat online so that we won't miss your message and contact you smoothly.